I was having problems with my generator a few years ago. I was getting an EC72 error. Chris in Texas tipped me off that the a potential problem with the main power relay. I spoked to Kohler and they confirmed there were some problems with the relay. I purchased a relay for about $5.00 and installed it myself. My problems went away. The relay is about 1inch square that looks like small black fuse block that you would plug into a fuse panel on your car. It sitst behind the control panel.
Looks like this (this is not the actual Kohler relay)
Re: Kohler 5ecd Generator shuts down - EC72
Looks like this (this is not the actual Kohler relay)
Re: Kohler 5ecd Generator shuts down - EC72
Hello All,
Just to let you know I have had the EC72 on a reoccurring basis. Would run then stop suddenly and show EC72. Would clear it and restart after a while would do it again. Kept progressively getting quicker and quicker to the point it wouldn't start, would try to start but then show EC72 right away.
1st fix by Kohler guys was to replace the K5 Main power relay. From the factory it was a cheap made in china no-name 30A relay. Was replaced by Bosch relay. The reason was the relay contacts were getting burnt and carbon build up on it, and wasn't getting power to the ECU on the back of the genny, it also started affecting the fuel pump at the end.
The 2nd time I got the EC72 about 5 months later, it was narrowed down to the 120 Ohm resister on the CAN bus, located closest to the front starboard side of the genny. A new resister was soldered into place and has worked like a champ ever since.
Hope this helps,
Chris
Just to let you know I have had the EC72 on a reoccurring basis. Would run then stop suddenly and show EC72. Would clear it and restart after a while would do it again. Kept progressively getting quicker and quicker to the point it wouldn't start, would try to start but then show EC72 right away.
1st fix by Kohler guys was to replace the K5 Main power relay. From the factory it was a cheap made in china no-name 30A relay. Was replaced by Bosch relay. The reason was the relay contacts were getting burnt and carbon build up on it, and wasn't getting power to the ECU on the back of the genny, it also started affecting the fuel pump at the end.
The 2nd time I got the EC72 about 5 months later, it was narrowed down to the 120 Ohm resister on the CAN bus, located closest to the front starboard side of the genny. A new resister was soldered into place and has worked like a champ ever since.
Hope this helps,
Chris